NETWORK ALARM UNITS Go back to the Catalog Synopsis
 
Equipements MEDICAL GAS NETWORKS CONTROL VISIO

Electronic signals of medical gas networks by VISIO concept, (linked to specification of the European EN 737-3 norm) is the solution to alert any defaults of medical gas networks. This system offers information about the gas pressures, together with a secure tracability of the failures. The analogic technology of the sensors allows a great precision even with the most difficult configuration of signal alarm units.







TECHNICAL DATA



VISIO PRINT printer

The VISIO PRINT prints each default (type, date and time) and also allows the display of all defaults to the VISIO 8 alarm unit by isting or "as it comes". The report will be a written proof to non conformity report for accredited companies.

• VISIO PRINT printer VAL 0900

Analogic Sensors

The analogic sensors technology is fully electronic (no "sticking", coalmining or mechanical dysfunctioning usually known for pressostats).
Numeric information transmitted to the unit allow an accurate calibration of the unit low limits.
A mounting system installed between the sensor and the pipe admits a maintenance even under pressure.

• Pressure sensor 0-16 atm VAL0300
• Depression vacuum -0.9 atm VAL0301
• Pressure sensor 0-250 atm VAL0302
• Mounting system for sensor 16 & 0.9 atm VAL0401
• 2 pairs coil Wire (50 ml) VAL1000

General control of VISIOSOFT database and VISIOTEL modem (on VISIO8 control alarm)

The VISIOSOFT is a powerful control software. Up to 50 alarm units, to remote parameter each alarm unit (possible external modification of data on each unit), centralisation of the defaults on the same printer, any problem at distance. The alarm units are together connected and to the computer by RS 485 BUS. The VISIOTEL modem dispatches the information by telephone for distant hospitals.

• VISIOSOFT supervision software VAL0700
• VISIOTEL transmission modem VAL0801

ALARM UNIT VISIO8

VISIO8 alarm unit manages 7 analogical inputs and 8 logical inputs (TOR). Its liquid crystal display with a graphic and numeric reading of each pressures allows a precise, quick and easy control to the medical staff and also for the technical departments. The VISIO8 alarm unit can be installed in operating theatre or resuscitation rooms with remote alarm unit in operating wards.

• VISIO8 alarm unit wall mounted box VAL 0004
• VISIO8 alarm unit wall integrated box VAL 0009
• VISIO8 battery (spare part) VAL 0601

Installation Maintenance

The VISIO 8 central alarm offers an easy connection access separate from the " mother card ". Possible connection by a large slot offering an easy connection to release connectors. This system also allows a possible changing of alarm without disconnecting the unit.
Different sizes of anti-confusion connectors avoiding any connecting error.
Supply power feeding 230 V - 1,5mm2 cable. All other wiring ( sensors and reports) are in "2 even cables" SYT type with screen.
Pre-programmed unit for a 4 primary/secondary gas station.

VISIO REPORT remote unit and VISIO RELAY unit (linked to VISIO 8 alarm unit)

The VISIO REPORT remote unit is defaults visual and audible remote (up to 5 gas in operating theatre with its BUS technology easy installation is offered (2 even wire connection).
VISIO RELAY allows to link 8 alarm units on a GB system (8 gas or 8 defaults). (VISIO RELAIS keeps the same design and features of the VISIO REPORT remote).

• VISIO REPORT remote unit wall mounted box VAL0100
• VISIO RELAY unit wall integrated box VAL0101
• Wall mounted box VAL0200
• Integrated box VAL0201
• 2 even coil Wire (50 ml) VAL1000

ALARM UNIT VISIO5

VISIO5 alarm unit manages 5 analogic or logic inputs (TOR). The concerned gas pressures blinks on liquid crystal display. Several green and red leds confirms the normal use or the default of concerned gas.
By its polyvalence you can also either use it for gas production (bottle, compressors) or inside hospital network control.

• VISIO5 alarm unit wall mounted box VAL 0001
• VISIO5 alarm unit wall integrated box VAL 0010
• VISIO5 battery (spare part) VAL 0002

Installation and maintenance

UNIBLOC Visio 5 unit with possible connection by bottom or rear. Release connectors of different sizes for avoiding any confusion.
Supply power feeding 230 V - 1,5mm2 cable. All other wiring ( sensors and reports) are in "2 even cables" SYT type with screen.
Pre-programmed unit for a 4 secondary gas network.

AFTER SALES SERVICE/TRAINING

Direct Line (+33) 328 160 488

Our qualified technicians are at your disposal for :
- Optimising the different network configurations
- Helping you with installation and programming
- Finding any eventual connecting default
- Training your technicians on system

Full free service (excluding external expenses in case)

Download this file in PDF format (134 Ko)Download the file
  Go back to the Catalog Synopsis
Head Office and Production Site - PARC EURASANTE - 310 rue Jules VALLES - 59120 LOOS - n° Tel : +33.328.16.04.80 - Fax : +33.328.16.04.89